A research team has unveiled a megawatt‑class Power Hardware‑in‑the‑Loop (PHiL) test bench that runs wind‑turbine converter and control systems while the wind‑turbine’s mechanical generator and the power grid are replaced by real‑time computer models.
The bench implements a distributed simulation: the aerodynamic rotor model runs on a remote device and feeds results across the Internet, while the grid model is linked through a dedicated fiber‑optic cable. This is the first time such geographically separated subsystems have been used together for certification‑relevant tests.
Operating the converter as the Device‑Under‑Test (DUT) keeps the mechanical and electrical parts of the turbine out of the loop. Instead, a real‑time simulation generates the turbine’s torque and speed, and a software emulator reproduces the power‑grid response. The inter‑site communication uses VILLASnode gateways that synchronize UDP packets with unique identifiers, keeping the average Internet latency below 10 ms.
Tests show that when no extra delay is added, the machine‑side power signal contains only a 4.22 % spectral distortion of the whole 2‑500 Hz bandwidth. Adding a 50 ms round‑trip delay raises the distortion to 14.55 %. The distribution system also keeps the grid‑side voltage stable: a no‑load test registered a total harmonic distortion of 0.33 % and a high‑frequency THD of 0.17 %, well within the FGW TR3 specification.
The benchmark power supply of the bench is 120 kW, which limits the ability to test large‑scale fault‑ride‑through events that need more DC‑link energy. The authors addressed this for the current experiments by installing a 6 F supercapacitor stack, but further increases in supply power or capacitor size would be needed for wider test coverage.
The team also built a detailed reference simulation that includes multiple generator models and reproduces machine‑side and grid‑side interactions, validating the overall PHiL setup.
This integrated architecture lets researchers run complex wind‑turbine failure scenarios without a full practical turbine, accelerating the design and certification cycle for next‑generation grid‑compliant turbines.